Hygienic HTM Compliant Air Handling Units - S
                                               Hygienic HTM Compliant Air Handling Units - Selection Guideelection Guide







    Max/Min air volumes are calculated at 350Pa external resistance allowance          RETURN AIR SIDE (Return ==> Exhaust)
    Eurovent Certified & ERP 2018 Compliant                                            Access Section with M5 Panel Filter, in tray (Electrostatic Powder Coated Aluminium), Accessories :
    Inner Sheet 0.8mm Stainless Steel                                                  Plate Heat Exchanger as above
    Outer Sheet Electrostatic Powder Painted Pre-Galvanized Steel                      304 SS Back Draft Dampers for Fan operation at reduced air flow
    Base 250mm High included in dimensions                                             Distance between Back Draft Damper and Fan Inlet Cones > 40cm
    Fresh Air (Ambient Side) Connection, Concealed Gear Type, Aluminium Dampers on the external surface   Fan + Motor combination to allow 75%+ of airflow even with one fan failure
    of the unit (External)                                                             Damper, Concealed Gear Type, Aluminium Dampers on the external surface of the unit. (External)
    Supply (Building Side) flanged connection                                          +250mm base frame if side by side orientation
    Exhaust Air (Ambient Side) Connection, Concealed Gear Type, Aluminium Dampers on the external
    surface of the unit (External)
    Return (Building Side) flanged connection                                          Individual selection for working point can be calculated for all of the above products, contact us
    Design Winter : -5C DB / 90%RH - 22C / 50%RH  -  Design Summer : 30C DB / 50%RH - 22C / 50%RH  for more information.

   FRESH AIR SIDE (Ambient ==> Supply).
    Damper, Concealed Gear Type, Aluminium Dampers on the external surface of the unit (External)
    Access Section, Light / Observation Glass
    Frost Coil , Copper Tubes, Tube Material Thickness 0.4mm / Finless / Connection Material :
    Copper / 304 SS Coil Frame  (Coil Air Off + 5C)
    Access Section with G4 Panel Filter, in tray (Electrostatic Powder Coated Aluminium), Accessories :
    Magnehelic Gauge / Light / Observation Glass
    Plate Heat Exchanger Dry Balanced Eff > 73%, Full Drain Pans and Bypass Dampers
    (No Face Damper on fins) (Aluminium Fins, No extra Coating)
    304 SS Back Draft Dampers for Fan operation at reduced air flow
    Distance between Back Draft Damper and Fan Inlet Cones > 40cm
    Fan + Motor combination to allow 75%+ of airflow even with one fan failure
    Cooling Coil, Copper Tubes Tube Material Thickness 0.4mm / Copper Fins 0.1mm  / Connection
    Material : Copper / 304 SS Coil Frame
    (Cooling Coil Air On, Unconditioned, ==> Air Off < 21C)
    Drop Eliminator (304 Stainless Steel Frame) in tray, 304 Stainless Steel Drain Pan.
    Access Section
    Heating Coil, Copper Tubes, Tube Material Thickness 0.4mm / Copper Fins 0.1mm / Connection
    Material : Copper / 304 SS Coil Frame
    (Heating Coil Air On, Conditioned by Heat Recovery, Air Off > 28 C)
    Access Section with F7 Bag Filter, in tray(Electrostatic Powder Coated Aluminium), Accessories :
    Magnehelic Gauge / Light / Observation Glass Flanged Duct Connection