Modular Air Handling Units - Selection Guide




                                        Heat Recovery Type    ERP 2018 = SFP<1.8     Amps        KW        Weight                      Dimensions (mm)
                                                                                                                                                                   DX Heating
                                                                                                                                                        DX Cooling
        Unit Configuration  Model Ref  Counterflow  Rotary  Min Capacity I/s Max Capacity I/s  3 x 400V  1 x 240V  (kg)  Length   Depth       Height    Capacity (kW)  Capacity (kW)
                          VEX4010RDX                          275         800         11,3      4,39        665         3114       1055       1409       15,0       24,0
                          VEX4020RDX                          415         1100        12,1      4,73        754         3114       1275       1409       18,2       29,1
                          VEX4030RDX                          695         1800        16,5       8,2        1002        3334       1549       1599       21,15      33,8
                          VEX4040RDX                          835         2150        16,6       8,5        1063        3334       1630       1699       29,2       46,7
                          VEX4050RDX                          1110        2600        19,3      10,84       1184        3434       1755       1844       34,5       55,2
                          VEX4060RDX                          1335        3150        20,3      14,64       1560        3614       1930       2169       48,25      74,0
                          VEX4070RDX                          1665        3800        23,4      14,64       1723        3894       2115       2169       56,35      90,2
                          VEX4080RDX                          1940        4350        25,8      16,24       2094        3894       2325       2494       76,10      121,8
                          VEX4090RDX                          2380        6000        34,4      24.74       2710        3894       2625       2744       104,0      166,4
                          VEX4100RDX                          3000        7400        41,6      28,19       3020        3894       2895       3024      130,25      208,4
                          VEX4010PDX                          275         525         9,1        3,37       679         3284       1055       1409       11,1       17,8
                          VEX4020PDX                          415         700         9,5        3,37       806         3284       1275       1409       14,7       23,5
                          VEX4030PDX                          695         1100        12,7       5,41       1055        3646       1549       1599       19,1       30,6
                          VEX4040PDX                          835         1450        12,5       5,41       1199        3786       1630       1699       27,5       44,0
                          VEX4050PDX                          1110        1650        15,5       8,66       1264        3786       1755       1844       31,7       50,7
                          VEX4060PDX                          1335        2100        14,3       5,93       1628        4394       1930       2169       44,5       71,2
                          VEX4070PDX                          1665        2400        20,1      14,64       1858        4674       2115       2169       50,3       80,5
                          VEX4080PDX                          1940        2700        25,8      16,24       2289        4816       2325       2494       65,5       104,8
                          VEX4090PDX                          2380        4000        23,4      70,77       2848        5199       2625       2744       93,1       149,0
                          VEX4100PDX                          3000        4800        35,0      28,19       3258        5199       2895       3024       114,5      183,2
                          VEX5020MB                           280         970       10,9 (14,1)  3,35 (5,2)  559 (575)  3357       1027       1434
                          VEX5050MB                           500         2500      16,0 (19,6)  6,29 (8,35)  921 (964)  3757      1417       1943
                          VEX5080MB                           700         3335      13,8 (23,1)  5,01 (10,39)  1117 (1204)  3757 (3837)  1947  1934
                          VEX5090MB                           1000        4915      23,1 (32,4)  10, 39 (15,73)  1312 (1640)  3997 (4557)  1947  2334
                          VEX5100MB                           1200        5195      23,1 (27,5)  10,32 (12,83)  1547 (1780)  4237 (4317)  2217  2334
                          VEX5130MB                           1500        6945      24,3 (36,5)  10,96 (17,98)  1843 (2005)  4397 (4557)  2217  2734
                          VEX5160MB                           1900        8610      24,0 (50,5)  10,84 (26,08)  2122 (2501)  4717 (4837)  2217  3334
                          VEX5180MB                           2300       10640      37,2 (63,2)  18,42 (33,34)  2570 (3038)  5077 (5477)  2217  3934

                          VEX5090MBAF                                     5400        35.5      15.14       1449        4352       1947       2334
                          VEX5100MBAF                                     6055        38.7      16.95       1598        3997       2217       2334
                          VEX5130MBAF                                     7385        44.6      21.89       1815        4432       2217       2734
                          VEX5160MBAF                                     9305        52.6      26.12       2144        4717       2217       3334
                          VEX5180MBAF                                    11665        63.4      31.55       2621        5237       2217       3934


      Max/Min air volumes are calculated at 250Pa external resistance allowance, F7 ePM1 65%, M5 Filters ePM10 50%, -5°C/80% with water 60/40; summer - 26°C/60% with water 6/12; mixing rate 30% for the
      units with mixing sections
      ERP 2018/SFP data are calculated in accordance with EU1253/2014 (the Ecodesign directive)
      Units are available in sections + flat pack for site assembly.
      Individual selection for working point can be calculated for all of the above products, contact us for more information.
   1   2   3   4   5   6   7   8   9   10