Modular Air Handling Units - Selection Guide
                                               Modular Air Handling Units - Selection Guide



                                       Heat Recovery Type      ERP 2018 = SFP<1.8  Amps        kW        Weight         Dimensions (mm) inc 1 coil    +Length   + length with 2 coils
       Unit Configuration  Model Ref  Counterflow  Rotary  Min Capacity l/s Max Capacity l/s  3 x 400V  3 x 400V  (kg)  Length  Depth     Height     with 1 coil  & spacing section
                         Exaeco 10                           830        2100        10,4       6,6        1120       2550       1620       2100        Inc        480
                         Exaeco 13                           1110       2800        16,4       8,0        1350       2690       1820       2250        Inc        480
                         Exaeco 17                           1650       3500        29,6       15,0       1650       2830       2090       2315        Inc        480
                         Exaeco 22                           2225       4750        46,4       22,0       1850       2873       2285       2510        Inc        480
                        Themover 180                         165        1440        10,0       9,7        665        2920       1115       1215        Inc        480
                        Themover 280                         225        2240        13,2       11,3       845        3130       1385       1475        Inc        480
                        Themover 400                         415        3200        17,3       15,5       935        3220       1455       1535        Inc        480
                        Themover 500                         555        4000        23,4       19,6       1120       3340       1655       1645        Inc        480
                         VEX4010R                            275        800         11,3       4,39       665        2265       1055       1409        480        924
                         VEX4020R                            415        1200        12,1       4,73       754        2265       1275       1409        480        924
                         VEX4030R                            695        1900        16,5       8,2        1002       2375       1549       1599        480        924
                         VEX4040R                            835        2250        16,6       8,5        1063       2375       1630       1699        480        924
                         VEX4050R                            1110       2720        19,3      10,84       1184       2375       1755       1844        480        924
                         VEX4060R                            1335       3200        20,3      14,64       1560       2665       1930       2169        480        924
                         VEX4070R                            1665       3900        23,4      14,64       1723       2845       2115       2169        480        924
                         VEX4080R                            1940       4850        25,8      16,24       2094       2845       2325       2494        480        924
                         VEX4090R                            2380       6400        35,4      25,74       2710       2845       2625       2744        480        924
                         VEX4100R                            3000       7915        41,6      28,19       3020       2845       2895       3024        480        924
                         VEX4010P                            275        550         9,1        3,37       679        2583       1055       1409        480        924
                         VEX4020P                            415        735         9,5        3,37       806        2583       1275       1409        480        924
                         VEX4030P                            695        1100        12,7       5,41       1055       2945       1549       1599        480        924
                         VEX4040P                            835        2,1         12,5       5,41       1199       3085       1630       1699        480        924
                         VEX4050P                            1110       1700        15,5       8,66       1264       3085       1755       1844        480        924
                         VEX4060P                            1335       2100        14,3       5,93       1628       3413       1930       2169        480        924
                         VEX4070P                            1665       2400        20,1      14,64       1858       3598       2115       2169        480        924
                         VEX4080P                            1940       3000        25,8      16,24       2289       3735       2325       2494        480        924
                         VEX4090P                            2380       4400        23,4      10,77       2848       4018       2625       2744        480        924
                         VEX4100P                            3000       5100        35,0      28,19       3258       4018       2895       3024        480        924

     Max/Min air volumes are calculated at 250Pa external resistance allowance, F7 ePM1 65%, M5 Filters ePM10 50%, -5°C/80% with water 60/40; summer - 26°C/60% with water 6/12; mixing rate 30% for the units with mixing sections.
     ERP 2018/SFP data are calculated in accordance with EU1253/2014 (the Ecodesign directive).
     Units are available in sections + flat pack for site assembly. Despatched in 2 Sections  Despatched in 3 Sections
     Individual selection for working point can be calculated for all of the above products, contact us for more information.